APC Back-UPS XS 700U
Linux config
apt install apcupsd
** /etc/default/apcupsd **
ISCONFIGURED=yes
/etc/apcupsd/apcupsd.conf
UPSCABLE usb
UPSTYPE usb
DEVICE /dev/usb/hiddev[[0-15]]
read status
jack@x4:~$ /sbin/apcaccess
APC : 001,036,0858
DATE : 2018-04-04 13:52:01 +0200
HOSTNAME : x4
VERSION : 3.14.14 (31 May 2016) debian
UPSNAME : x4
CABLE : USB Cable
DRIVER : USB UPS Driver
UPSMODE : Stand Alone
STARTTIME: 2018-04-04 13:24:46 +0200
MODEL : Back-UPS XS 700U
STATUS : ONLINE
LINEV : 224.0 Volts
LOADPCT : 0.0 Percent
BCHARGE : 100.0 Percent
TIMELEFT : 285.8 Minutes
MBATTCHG : 5 Percent
MINTIMEL : 3 Minutes
MAXTIME : 0 Seconds
SENSE : Medium
LOTRANS : 140.0 Volts
HITRANS : 300.0 Volts
ALARMDEL : 30 Seconds
BATTV : 13.8 Volts
LASTXFER : No transfers since turnon
NUMXFERS : 0
TONBATT : 0 Seconds
CUMONBATT: 0 Seconds
XOFFBATT : N/A
SELFTEST : NO
STATFLAG : 0x05000008
SERIALNO : 3B1752X08311
BATTDATE : 2017-12-28
NOMINV : 230 Volts
NOMBATTV : 12.0 Volts
NOMPOWER : 390 Watts
FIRMWARE : 924.Z3 .I USB FW:Z3
END APC : 2018-04-04 13:52:01 +0200
USV/UPS IBM - 9910-140
Eigenschaften
=>identify
Global UPS For IBM
Model: LI????VA
Unit ID:
Serial #:
Version: 4.01
Released: 04/01/99
RS-232 Kommandos
Siehe auch: (ist nicht identisch aber
viele Sachen ähnlich)
Status - Statusabfrage
=>Status
System status report for LI????VA [] (#)
Monday, January 02, 1996 - 07:41:48
Line status | Load status | UPS status | Totals
--------------|---------------|---------------|---------------
V In 225 | I Out .1 | Mode: OnLine | SysHrs 00019
V Out 223 | VA Out 22 | Tap: Bypass | InvMin 0042.7
Freq 50.00 Hz | Watts 0 | V Batt 52.7 | #PwrOut 2
PF 1.00 ---- | FullLoad% 001 | Runtime 55m | #OvrLds 0
Front panel: - B - |
Last battery power run duration: 2562 seconds.
Active alarms:
(None)
cd -- contdisplay
Gibt bis Unterbrechung (z.b. \<Return> senden) die angegebenen Parameter aus.
=>cd 8 9
08 Freq 49.97 Hz
09 Runtime 55m
08 Freq 49.97 Hz
09 Runtime 55m
08 Freq 49.97 Hz
09 Runtime 55m
08 Freq 49.96 Hz
09 Runtime 55m
08 Freq 49.97 Hz
09 Runtime 55m
oder cd 1 7 8 20
(Vin Vbatt Freq #pwroutages)
command - Verfügbare Kommandos
=>command
? 123DCP AlarmsHelp AlarmLog AlarmStatus
AlarmTest ChargerMode ClearAlarms ClearHistory ClearLogs
ClearPassword ComMands ContDisplay ContStatus DAte
DEFAULT DeLay Display eXtendedHistory Format
FormatConfig FormatParam HElp History Identify
InverterLog LocK Logs MEMory Message
Off PRogram Parameters ParamKeywords PassWord
PrinT RESET RESTART ShutDown SHutup
Status SystemMode SystemTeST TEST Time
TurnOFF UnLock Unshutup DB26 ContDB26
eXtendedHistory
=>eXtendedHistory
97.0 228.0 217.0 230.0 16.10 58.10 21 179
password - Wechseln in Service Mode
2639 ist anscheinend Default Passwort
=>password 2639
Serv => .... -jetzt in Service Mode-
Serv => password
=> .... -jetzt wieder normal
systemmode
"Online" USV Schaltet die USV auf Batteriebetrieb.
Serv => systemmode inverter
System mode: Inverter
Serv =>
{Inverter: On}
Automatik
Serv => systemmode auto
System mode: Auto
Serv =>
{Inverter: Off}
Parameters / paramkeywords
Parameters ist wie paramkeywords nur ohne Benamung der Felder
=>paramkeywords
00 Time 08:03:19 Time
01 V In 225 acVoltsIn
02 V Out 224 acVoltsOut
03 - B - | DiSplay
04 I Out .1 acampsiOut
05 VA Out 22 VAout
06 CPM V OUT .0 DCVOut
07 V Batt 52.7 VBattery
08 Freq 49.99 Hz Frequency
09 Runtime 55m RunTime
10 Date 01/02/96 Date
11 Day 1)Mon DAYofweek
12 PWLvl 0)None PassWordLevel
13 Model Name
LI????VA ModelName
14 Serial Number
SerialNumber
15 Unit ID
unitIDentify
16 FullLoad% 001 fullLoad
17 Watts 0 Watts
18 PF 1.00 ---- PowerFactor
19 CrestF 1.44 CrestFactor
20 #PwrOut 4 PoWeROuts
21 #OvrLds 0 OverLoads
22 SysHrs 00019 SystemHours
23 InvMin 0043.1 InverterMinutes
24 #Bad PW 2 BadPassword
25 BTTime 02:00 BattTestTime
26 BTIntervl 14 BattTestInterval
27 KeyClic 1)On KeyClick
28 BeepTone 0)Lo BeeperTone
29 Ferro 0)Off
Min volts counts now 7Bh REServed
30 Min Volts Count 7Bh MINDcv
31 MaxDCV 57.9 MAXDcv
32 MinACVI 224 MINacVI
33 MaxACVI 225 MAXacVI
34 MinACVO 221 MINacVO
35 MaxACVO 229 MAXacVO
36 Min VA 22 MINVA
37 Max VA 22 MAXVA
38 Low Rntm 3 LowRuntime
39 AutoRst 60 AutoRestart
40 Nom VIn 230 NomacVoltsIn
41 Nom VOut 230 NomacVoltsOut
42 Low VOut 191 LowVoltsOut
43 Hi VOut 259 HiVoltsOut
44 Boost V 172 BoostVolts
45 Bypass V 200 BYpassVolts
46 Buck V 251 BucKVolts
47 InverterV 277 InverterVolts
48 BBHyst 4 BuckBoostHyst
49 RatedVA 1400 RatedVA
50 RatedW 1400 RatedWatts
51 CBLimit 384 CBLimit
52 Nom Freq 0)50 NomFrequency
53 AutoFrq 1)Yes AutoFrequency
54 LowFreq -3.00 LowFrequency
55 HiFreq +3.00 HighFrequency
56 Slew Rate 50 SlewRate
57 PhaseWin 500 PhaseWindow
58 FreqSens 3 FreqSensitivity
59 LineSens 10 LineSensitivity
60 FaltSens 1)Hi FauLTSensitivity
61 NomDCV 48.0 NomDCVolts
62 LowBatt 38.4 LowBattery
63 NrLoBatt 43.2 NearLowBattery
64 HighBatt 61.4 HighBattery
65 Maint V 53.2 MaintenanceVolts
66 Eqlz V 56.0 EqualizeVolts
67 ConITm 6 ConstantITime
68 ConVTm 240 ConstantVTime
69 EqlzTm 1080 EqualizeTime
70 EqlzInvl 30 EqualizeInterval
71 BaudRt 1)600 BauDrate
72 WordFmt 0)8N1 WordFormat
73 PNP 1)Yes PlugNPlay
74 TxHS 1)Yes TransmitxHs
75 RxHS 1)Yes ReceivexHs
76 Prompt 1)Yes PRompt
77 Echo 1)Yes EChoback
78 AutoMsg 1)Yes AutoMessage
79 ID Msg 1)Yes IDentifyMessage
80 Con Ctrl 15 ConsoleControl
81 AlmCPol 0)Neg AlarmConPolarity
82 AlmEnbl 65535 AlarmcEnables
83 ShdnPol 0)Neg ShutdownPolarity
84 ShdnDbnc 5.0 ShutdownDeBounce
85 ShdnDly 30.0 ShutdownDeLay
86 EPO Pol 0)Neg EPOPolarity
87 EPO Dbnc .2 EpoDeBounce
88 EPO Dly .1 EpoDeLay
89 InvCPol 0)Neg InvContPolarity
90 InvCDly 150 InvContDelay
91 OnTime 08:00 powerONTime
92 OnTmDays 0
SFTWTMS: 0000000 ONtimeDays
93 OffTime 17:00 powerOFfTime
94 OffTmDays 0
SMTWTFS: 0000000 OFftimeDays
95 POMode 1)On PowerOnMode
96 XferDly 1.5 XferDelay
97 TapSwDly .2 TapSwitchDelay
98 TapSwPh 8 TapSwitchPhase
99 GuardSt 27 GuardpStart
100 GuardEnd 6 GuardpEnd
101 ChargdV 51.2 CHargedVbattery
102 RntmK1 850 RuntimeK1
103 RntmK2 2 RuntimeK2
104 RntmK3 90 RuntimeK3
105 RntmK4 19 RuntimeK4
106 BatSavV 36.0 BatterySaverV
107 CycChg 1)Yes CycleCHarger
111 CFACVIN 115 CFacVIN
112 CFACVID 72 CFacVID
113 CFACVON 116 CFacVON
114 CFACVOD 76 CFacVOD
115 CFA AO N 200-230 50 CFacAONHiV
116 CFA AO N 100-120 60 CFacAONLowV
117 CFA AO D 200-230 43 CFacAODHiV
118 CFA AO D 100-120 27 CFacAODLowV
119 CFDCVN 166 CFDCvN
120 CFDCVD 68 CFDCvD
121 RefNom 170 ReferenceNominal
122 XfmrRes 0 XfmrResistance
123 Inhibits 00h INHibits
124 RefLevel 170 ReferenceLevel
125 Num Batts 2 NumberBatteries
142 DBTest 0)No DBTests
146 LRefNominal 174
LRefScaled 174
147 CStart 0)Neg
148 Dev1 0
149 Sum VI Peaks
0000h
150 Lastflags 17
151 TestFlags 0
152 ConditionFlags 0
153 CPM RAW Counts 0
154 P5G contents = 0
155 AVG Flsgs Content 80h
Nicht implementiert
- Logs
- AlarmLog
- InverterLog
- ChargerMode
RS-232 Adapter
Baudrate steht in den Parametern.
Sub-D 9 pol. male (USV) | Sub-D 9 pol. female (PC) | Funktion | genormte Farben |
---|---|---|---|
1 | 3 | Tx (Vom PC aus) | orange |
2 | 2 | Rx (Vom PC aus) | rot |
4 | 5 | GND | grün |
http://de.wikipedia.org/wiki/RS-232
Rotronic/Roline LineSecure 700
Dry Contact Signals
- PIN2: Contact with PIN4 when AC fault.
- PIN5: Contact with PIN4 when Battery low
- PIN4: Common GND of PIN2, 5
- PIN6: Input high level over 500ms to turn off UPS.
- PIN7: GND of PIN6
RS-232
Adapter Schematic
- PIN9: TX
- PIN6: RX
- PIN7: GND
- BAUD RATE : 2400 bps
- DATE LENGTH : 8 bit ASCII Code
- STOP BIT : 1 bit
- PARITY : NONE
- Data Stream :
- a. Manufacturer
- b. UPS Model
- c. CPU Version
- d. Voltage Rating
- e. Current Rating
- f. Input Voltage
- g. Output Voltage
- h. Input Frequency
- i. Output Frequency
- j. Load Level
- k. Battery Level
- l. Temperature
- m. Schedule ON/OFF command
- n. Self test command
- o. Shutdown command
CMD | description | example return value |
---|---|---|
a | Manufacturer | |
b | UPS Model |